Pressure Rise Method.

System must be evacuated to less than 1.0 Millibar absolute. After the system has been evacuated the vacuum pump should be isolated from the system. As a guide, with constant ambient conditions, the vacuum should not rise more than 0.13 Millibar in one hour. A greater rate of rise may indicate a leak or the … Continue reading Pressure Rise Method.